Browse all practice questions for the Motorola Standards and Guidelines for Communication Sites (R56) Practice Test. Search by topic, open any question and review its full explanation, then test yourself in the practice quiz.

Motorola Standards and Guidelines for Communication Sites (R56) Practice Test course image
More practice questions

These questions are part of the practice quiz. Start practicing

  • Class I Lighting Protection System (LPS) requires a #2 AWG Copper down conductor.
  • Which option is NOT listed as a major SPD site entrance?
  • What is the suggested height of coaxial cables to enter facility above facility door?
  • What is the minimum thickness required for the External Ground Bus Bar?
  • Which statement about building-entry bonding is correct?
  • What is the required depth for the grounding wire mesh?
  • What is the minimum gauge for a single item bonding conductor?
  • Ice Bridge Grounding: Which combination of gauges is specified for grounding and bonding the ice bridge respectively?
  • The 24 inch measurement is used to determine which practice?
  • Which statement is correct about bonding in the context of Separately Derived Systems?
  • Distance Ratio Squared describes the energy coupling into a building as distance changes.
  • What is the minimum separation between the top of the equipment rack and the bottom of the cable tray?
  • Should grounding conductors be allowed to daisy chain in this setup?
  • Which of the following accurately describes conductors in drop ceilings?
  • BackBone Bonding Conductor bonds multiple Bonding Backbone Conductors.
  • The BackBone Bonding Conductor bonds what?
  • PDU stands for Power Distribution Unit.
  • Where should Conductive Anti Oxidant Compound be used?
  • What is used to bond detachable metallic parts of equipment cabinets?
  • Which conductor size is designated as the single item bonding conductor in this standard?
  • What does SPD stand for in electrical protection terminology?
  • What does energy coupling describe regarding distance?
  • Breakers and receptacles have to be labeled and correlated at the panel.
  • Ice Bridge Grounding: The bridge should be bonded to each support post using which gauge?
  • Which statement best describes a Type B Standard Duty Site?
  • Secondary Neutral-to-Ground bonds are allowed only with a Separately Derived Power Source.
  • Minimum fiber bending radius equals 10 times the diameter. If diameter is 0.25 inches, what is the radius?
  • What is the minimum vertical clearance from the top of the cable tray to the ceiling?
  • Is a site with no tower considered exposed to lightning?
  • For grounding electrode conductors, which splicing methods are permitted?
  • Class II Lighting Protection System (LPS) requires a #2/0 AWG Copper down conductor.
  • Communication wires can be attached to electrical conduit or raceways. True or False?
  • Which length range applies to a #2 AWG bonding conductor?
  • Should the DC Power System be installed closest or farthest to the PBB?
  • Ground rods shall be made of copper-clad steel, solid copper, hot-dipped galvanized steel or stainless steel. True or False?
  • What is the required ground resistance for a Type A Light Duty Site?
  • Concrete Reinforcing Steel, Water Pipe Systems, Metallic Pathways, or Conduits SHALL NOT be used as a bonding backbone conductor.
  • UPS stands for Uninterruptible Power Supply.
  • Tower Ground Bus Bars must be installed in relation to communication cable ground kits how?
  • For Operator Position SBB bonding, which gauge is specified for runs under 13 feet?
  • Underground water pipe can serve as grounding electrode if in direct contact with earth for how many feet?
  • Bonding conductors ______ decrease in size as the bonding path moves closer to the termination point of the GES.
  • Are split bolt connections allowed for grounding connections?
  • What is the required distance from a tower for the ground ring?
  • What is the required connecting method for grounding electrode conductors?
  • Is R56 a Motorola proprietary standard?
  • Within 24 inches of building entry, alarm circuits terminate to which device?
  • Ground plates thickness
  • What is the proper separation between service conductors and Tx lines?
  • Which statement best describes the bending and routing requirements for grounding conductor runs?
  • Which statement about raised floor securing is correct?
  • Objectionable Current is defined as which of the following?
  • Within 2 feet of the grounding down conductor, consistent AWG size should be used to the MRPLPR.
  • Which statement best describes the placement of the DC Power System relative to the PBB?
  • What is the minimum conductor size for the PBB?
  • Which bonding feature is installed in all equipment shelters/rooms for perimeter bonding?
  • A generator is considered Separately Derived System when the Automatic Transfer Switch breaks the neutral conductor.
  • Which insulation requirement applies to the PBB?
  • What is the required working space height?
  • In metallic conduit, conductors should be jacketed.
  • For Operator Position SBB bonding, which gauge is specified for runs under 10 feet?
  • Where is the concrete encasement located for a concrete encased electrode?
  • Where should line bonding at a building entry be placed?
  • For #6 AWG bonding conductor, what is the length range?
  • There shall be only one grounding electrode system, and all metallic items shall be bonded to it. True or False?
  • Which AWG size corresponds to a length of 53-66 ft?
  • Within how many inches of the RF line entrance should the PBB be located?
  • Which statement best describes ground rod placement?
  • What jacket/marking options are acceptable for interior bonding/grounding conductors?
  • What is the minimum working space width?
  • What gauge conductor should be used to bond each leg of a self-supporting tower?
  • Which materials are acceptable for ground plates?
  • What is the specified length for #3/0 AWG conductors?
  • What are the grounding conductor protection requirements?
  • Conductors shall be secured at no greater than how many feet?
  • SBB stands for which term in the grounding and bonding standards?
  • Which of the following is a valid major SPD site entrance?
  • What is the PBB thickness as specified?
  • LPS stands for Lighting Protection System.
  • Safety Kits shall include acid resistant bib type apron, acid resistant full-face shield, acid resistant gloves, acid neutralizing compound, and non-expired eye wash solution.
  • What is the maximum distance allowed between ground rods placed at corners?
  • What size should the single object above-ground external grounding conductor be?
  • Which systems must be bonded to the grounding electrode system?
  • What is the recommended Tx Line Bonding Distance?
  • Distance from a structural expansion connector to the adjacent side where a support shall be located?
  • What is the Vault site category used for?
  • What is the specified length for #2/0 AWG conductors?
  • Which bonding methods are allowed for the Tower Ground Bus Bar?
  • How deep must ground rods be buried below finished grade?
  • Raised Floor Conductor Securing when placed directly on sub floor must be at intervals no greater than?
  • For #4 AWG bonding conductor, what is the length range?
  • To bond the SBB to the PBB, what copper gauge is specified?
  • What is the purpose of the Bonding Backbone Conductor?
  • What are the requirements for Tower Ground Bus Bars?
  • Increasing the distance between tower and building will raise or reduce the susceptibility of damage due to the lightning?
  • Which conductor size is used to bond the ground rod to the cabinet?
  • What is the minimum length of a ground rod?
  • Secondary SPD bonding for telco, data, and control circuits shall be bonded using which gauge/length options?
  • What size is specified for multiple objects of above-ground external grounding conductors?
  • What grid size is specified for the grounding wire mesh?
  • Hanta Virus is described as a dangerous respiratory illness related to Ebola. How is it contracted and what is its approximate mortality rate?
  • Which option correctly lists a component that is included in site safety kits?
  • What is the minimum working space depth?
  • Histoplasma is described as a fungus that lives in which environment?
  • Which set describes the transmitter protections correctly?
  • Class II LPS is applicable when the building exceeds 75 feet in height.
  • Bonding Jumpers are typically what gauge and maximum length?
  • When solar panels are used, batteries should be able to power the site for how long without wind or solar?
  • What is the minimum SBB height specified in the standards?
  • For #3 AWG bonding conductor, what is the length range?
  • Ground rods not driven straight down or at 45 degrees need to be buried horizontally how deep?
  • Site Category: Building is defined as a permanent structure on foundation, suitable for human occupancy and contains equipment.
  • MRPLPR stands for Main Roof Perimeter Lighting Protection Ring.
  • IPBB Height is typically at what height?
  • GES stands for Grounding Electrode System.
  • At what angle should bonding conductors cross other cables?
  • IPBB stands for what?
  • In lightning prone locations, which conductor size should be considered?
  • What is the specified length for #1/0 AWG conductors?
  • What material should be used for Tower Ground Bus Bars when not protected against precipitation runoff?
  • PBB stands for Primary Bonding Bar.
  • Which site category is used for support communications equipment?
  • What is the minimum height above grade that grounding conductors must be protected?
  • Which AWG size corresponds to a length of 67-84 ft?
  • Which conductor size is designated as the bus conductor in this standard?
  • What is the maximum recommended PBB conductor length and splice condition?
  • Which bonding method is allowed for PBB connections?
  • Outer shields of Telco Cables serving the Operator Position shall be bonded using which gauge/length options?
  • What is the required distance from a building for the ground ring?
  • Interior bonding/grounding conductors must be kept a minimum distance from other cables and connectors, except at which location?
  • Which site category contains communications equipment and related support systems and is suitable for temporary human occupancy during equipment install and maintenance?
  • How many Neutral to Ground bonds are allowed?
  • Interior bonding/grounding conductors are made of which material by default, unless another material is specified?
  • Generators are required to be equipped with which alarms?
  • Stainless Steel Hardware Series used unless specified.
  • Ice Bridge Grounding: Each support must be grounded using which gauge copper?
  • How should ground rods be spaced relative to each other?
  • What is the minimum distance for grounding metallic objects relative to the external grounding electrode system?
  • What compound is used for bonding tinned connections to steel, galvanized steel, or aluminum?
  • What is the interior lighting minimum?
  • Supplementary Bonding Network/Grid uses what gauge? Can flat be used?
  • Where should all utility entrances be located?
  • Generator grounding: Additional ground rod is needed if the generator is more than how many feet from the building?
  • Single Point Grounding is the concept of bonding all equipment to a common point, commonly PBB.
  • What is the minimum PBB height specified in the standards?
  • Raised Floor Conductor Securing on pedestal must be at least at what interval?
  • Each transmitter should have which three protections?
  • For monopole towers, how many grounding conductors of #2 AWG copper are required?
  • IPBB Requirements include what?
  • The first disconnecting means is the location where the Neutral-to-Ground bond is permissible.
  • How should unused ports in the entry plate be sealed?
  • What fire extinguishers are required on site?
  • For bonding the Operator Position SBB, what gauge is specified for runs below 13 feet?
  • What is the minimum depth below finished grade for a ground rod?
  • Site Category: Shelter is defined as a permanent structure on foundation, contains communications equipment and related support systems, and is suitable for temporary human occupancy during maintenance.
  • The primary purpose of bonding all equipment together is to reduce or eliminate a potential difference between conductive materials.
  • What is the minimum ceiling height when using 7.5ft racks?
  • Separately Derived Systems shall be bonded on the secondary side of the unit.
  • Type 3 SPDs, PDUs, and UPS Chassis do require bonding to the Operator Position SBB.
  • Detachable Cabinet Doors or other detachable metallic objects use which gauge for bonding?
  • For #2 AWG bonding conductor, what is the length range?
  • Receptacle strips are allowed to have an ON/OFF switch provided the switch is covered.
  • How far should ground rods be spaced?
  • Which of the following items must be bonded to the Operator Position SBB?
  • In high lightning areas, what conductor size is recommended for the PBB?
  • Generators are required to be equipped with Engine High Temp Alarm/Shutdown and Low Oil Pressure Alarm/Shutdown.
  • How should the wire mesh be secured?
  • Ground rods shall be installed closer or farther than 6 feet apart?
  • For #1 AWG bonding conductor, what is the length range?
  • Bare Conductors shall be supported in what fashion?
  • What is the preferred shape and approximate size for the Single Point Entry Window area?
  • Rooftop Communications Shelters shall contain an Internal Bonding and Grounding System (IBGS).
  • What minimum gauge is recommended for bonding jumpers for detachable metallic parts of equipment cabinets?
  • What is the minimum conductor gauge for a bus conductor in this practice?
  • Connection between Building Ground Ring and Tower Ground Ring
  • What is the minimum bending radius specified for grounding conductor runs?
  • How many extension blocks or receptacle strips are allowed on the same branch circuit?
  • What is the specified length for #4/0 AWG conductors?
  • What is the minimum diameter of a ground rod?
  • Which site category houses communications equipment and related systems only and can be fully or partially buried?
  • The 66 Block is categorized as which type of component?
  • Is the statement 'Each leg of a self-supporting tower should be bonded using a #6 AWG conductor' true or false?
  • Which statement BEST describes Histoplasma habitat?
  • Government and Local Code take precedence over R56.
  • External Ground Bus Bar requirements specify what characteristics?
  • In a DC plant, what gauge must the SBB to PBB connection use?
  • What material is recommended for guy wiring bonding?
  • Is it permissible to use the entry plate holes for tower light power, building ground, and control cables?
  • Reducing the height at which RF Tx lines leave the tower and enter the building will reduce the susceptibility of lightning damage.
  • Class I LPS requires the building height not to exceed 75 feet.
  • Cables should be supported when spanning beyond what distance?
  • What is the minimum Size for Single Line SPD?
  • Which measurement corresponds to working space height?
  • Bond additional fence posts to limit the distance between bonded posts to 40 ft. True or False?
  • Conductors should be supported at what interval in cable tray?
  • Concrete Encased Electrode requirements specify how much concrete encasement?
  • Which of the following is a major SPD site entrance?
  • Which site category is described as occasionally prewired and pre-equipped?
  • What is the minimum size for an equipment bonding conductor?
  • Rooftop tower bonding to the Main Roof Perimeter Lighting Protection Ring requires at least two opposing conductors.
  • What is the required size for the below-ground external grounding conductor?
  • Bonding Backbone Conductor extends through building connecting which components?
  • Ground plates shall be made of what materials?
  • IPBB support requirements specify clearance from wall and spacing.
  • Ground Ring Conductor
  • Ground rods must be buried to satisfy which condition?
  • What is the bend radius specified for the ground ring?
  • For bonding the Operator Position SBB, what gauge is specified for runs below 10 feet?
  • What is the cabinet ground ring distance from the foundation?
  • The strengthening requirement for the ring connections is to use copper in at least how many points between Building Ground Ring and Tower Ground Ring?
  • Which statement most accurately describes a ground ring conductor?
  • Which disease is contracted by human contact with rodent waste and has about 50% mortality?
  • Which bonding method should be used for tower structure ground conductors unless directed otherwise by the manufacturer?
  • How far from the PBB does an RF Tx Cable entry have to be to require an Entry Point SBB?
  • What is the target ground resistance for a Type B Standard Duty Site?
  • Which materials are acceptable for the grounding wire mesh?
  • Which statement correctly describes detachable metallic objects bonding?
  • Under-floor cable trays can be bonded to which grid if present?
  • Which material SHALL NOT be used as a bonding backbone conductor?
  • What does SPD stand for in this context?
  • The working space must allow cabinet doors to be opened to 90 degrees.
  • Which site category is intended to house only communication equipment and related systems and is sometimes prewired?
  • Type B2 Extra Duty Site is best described as which of the following?
  • Which of the following is a correct pairing of AWG size and its maximum length?
  • What does RBB stand for in the context of site bonding?
  • What is the cable and conductor securing interval?
  • How many grounding rods are recommended to meet the grounding goal?
  • What is the minimum separation between the top of the cable tray and the ceiling?
  • What is the target ground resistance for a Type B2 Extra Duty Site?
  • What is the required depth for the radial grounding conductor?
  • Operator Positions often require a bonded SBB.
  • Rooftop conductor bonding methods include exothermic, irreversible or other fittings listed for use in Lighting Protection Systems (LPS).
  • Which site category is suitable for temporary human occupancy during equipment installation and maintenance?
  • If fiber diameter is 0.3 inches, what is the minimum bending radius?
  • If the PBB is not located in the equipment room, where should the cable tray be bonded?
  • What is the recommended minimum PBB length according to the specs?
  • For side-mounted antennas, a single ground conductor may be used, but two down conductors are recommended when practical.
  • What is the minimum wire size for a multiple-line SPD?
  • Site Category: Cabinet/Enclosure is defined as housing communication equipment and related systems only, and is occasionally prewired and pre-equipped.